Sunny Central 500HE-US

Search green products
Search green companies
Sunny Central 500HE-US
Central Inverters
SUNNY CENTRAL- High Tech for solar power stations
We have developed the Sunny Centrals specially for use in large PV power stations and open-field plants. Hence they possess completely special properties. String monitoring, capacity for teamwork and the ability to feed into the medium-voltage power grid make them first choice for PV systems with homogenous structure.
Sunny Central 500HE-US
The ideal solution for PV power stations in North America
Individual performance at an industrial level: In combination with an external transformer, the Sunny Central 500HE-US can be connected with any imaginable grid, which it also actively supports with the new grid management function. The outdoor enclosure with OptiCool cooling concept and the separate connection area ensure simple installation and low system costs. With its peak efficiency of 98.6 %, it outdoes all other devices in its performance class. SMA also supplies complete megawatt skids with two inverters and external AC/DC disconnectors located centrally in a Disconnect Unit and a transformer.
|
High yields
|
Strong peripherals
|
Low system costs
|
Grid management included
|
|
Sunny Central 500HE-US |
|
| Input (DC) | |
| Max. DC power (@ cos φ=1) | 513 kW 1) |
| Max. input voltage | 600 V |
| MPP voltage range | 330 V – 600 V |
| Rated input voltage | 380 V |
| Minimum input voltage | 330 V |
| Max. input current | 1600 A |
| Number of independent MPP inputs | 1 |
| Number of DC inputs | 6 – 9 |
| Output (AC) | |
| Rated power (@ 25 °C) / nominal AC power (@ 50 °C) | 500 kVA / 351 kVA |
| Nominal AC voltage / range | 200 V / 180 V – 220 V 2) |
| AC power frequency / range | 60 Hz / 59.3 Hz ... 60.5 Hz |
| Rated power frequency / rated power voltage | 60 Hz / 200 V |
| Max. output current | 1470 A |
| Max. THD | 3 % |
| Power factor at rated power / | > 0.99 / |
| adjustable shift factor | 0.9 leading ... 0.9 lagging |
| Feed-in phases, connection phases | 3 / 3 |
| Efficiency 3) | |
| Max. efficiency / European efficiency / CEC | 98.6 % / 97.9 % / 98.0 % |
| Protection | |
| Input side disconnection device | Motor-driven contactor |
| Output side disconnection device | AC circuit breaker |
| DC overvoltage protection, AC overvoltage protection | opt. / opt. |
| Grid monitoring | yes |
| Ground fault monitoring | yes |
| General Data | |
| Dimensions (W / H / D) |
2562 / 2277 / 956 mm (101 / 90 / 38 inch) |
| Weight | 1800 kg |
| Operating temperature range | -25 °C ... +50 °C / -13 °F ... +122 °F 4) |
| Noise emission | 59.3 db(A) 5) |
| Max. self-consumption (in operation) / self-consumption (at night) | 1700 W / < 110 W |
| Cooling concept | OptiCool |
| Degree of protection | NEMA 3R |
| Application | Unprotected outdoors |
| Maximum permissible value for relative humidity (non-condensing) | 15 % ... 95 % |
| Maximum operating altitude above MSL | 4000 m 6) |
| Fresh air consumption | 3000 m³/h |
| Features | |
| Display | LC graphic display |
| Communication interfaces | Ethernet, modbus, TCP, analog |
| Internal power supply transformer | yes |
| PV plant monitoring | Optional (via Sunny Portal) |
| Color of enclosure / door / base / roof | RAL 9016 / 9016 / 7005 / 7004 |
| Certificates and approvals (more upon request) | EMC conformity according to FCC, Part 15, Class A, UL 1741, UL 1998, IEEE 1547 |
| Type designation | SC 500HE-US |
|
1) Specifications apply to irradiation values at STC 2) AC voltage range for full active power: 196 V – 210 V 3) Measured without internal power supply at VDC = 330 V 4) Max. temperature at nominal conditions +45 °C / +113 °F 5) Sound pressure level at a distance of 10 m 6) No reduction in power up until 1000 m, afterwards 5 % per 1000 m |
Additional Information
- manufacturer: SMA Solar Technology / Germany /