Sunny Central 250 / 250HE / 350

Search green products
Search green companies
Sunny Central 250 / 250HE / 350
Central Inverters
SUNNY CENTRAL- High Tech for solar power stations
We have developed the Sunny Centrals specially for use in large PV power stations and open-field plants. Hence they possess completely special properties. String monitoring, capacity for teamwork and the ability to feed into the medium-voltage power grid make them first choice for PV systems with homogenous structure.
Sunny Central 250 / 250HE / 350
Direct connection to the low-voltage grid
The proven Sunny Central 250 and 350 allow operators of medium and large-scale PV power stations to achieve excellent solar yields, especially in ground-mounted systems or roof systems with homogeneous structures. The central inverters have 5, 8 or 12 fused inputs for the DC distribution boards and several devices can be connected together on the AC side, making megawatt systems possible. Whereas the Sunny Central 250 and 350 feed directly into the low-voltage grid, the Sunny Central 250HE can be connected directly to a mediumvoltage transformer.
Reliable
- Motor-driven DC disconnector
- DC and AC overvoltage protection
Informative
- Easy remote querying
- Status messages can be sent via e-mail or SMS
Optional
- String failure detection
- Extended DC input voltage range up to 1000 V
|
Sunny Central 250 |
Sunny Central 250HE |
Sunny Central 350 |
|
| Input (DC) | |||
| Max. DC power (@ cos φ=1) | 262 kW | 261 kW | 369 kW |
| Max. input voltage | 880 V / 1000 V optional | 880 V / 1000 V optional | 880 V / 1000 V optional |
| MPP voltage range (@ 25 °C) | 450 V – 820 V 1) | 450 V – 820 V 1) | 450 V – 820 V 1) |
| Rated input voltage | 500 V | 500 V | 500 V |
| Minimum input voltage | 450 V | 450 V | 450 V |
| Max. input current | 591 A | 591 A | 800 A |
| Number of independent MPP inputs | 1 | 1 | 1 |
| Number of DC inputs | 8 | 8 | 12 |
| Output (AC) | |||
| Rated power (@ 25 °C) | 250 kVA | 250 kVA | 350 kVA |
| Nominal AC voltage | 360 V – 440 V | 243 V – 297 V | 360 V – 440 V |
| AC power frequency | 50 Hz, 60 Hz | 50 Hz, 60 Hz | 50 Hz, 60 Hz |
| Rated power frequency / rated power voltage | 50 Hz / 400 V | 50 Hz / 270 V | 50 Hz / 400 V |
| Max. output current | 361 A | 535 A | 505 A |
| Max. THD | < 3 % | < 3 % | < 3 % |
| Power factor at rated power | 1 | 1 | 1 |
| Feed-in phases, connection phases | 3 / 3 | 3 / 3 | 3 / 3 |
| Efficiency 2) | |||
| Max. efficiency / European efficiency | 96.1 % / 95.2 % | 97.5 % / 96.7 % | 96 % / 95.2 % |
| Protection | |||
| Input side disconnection device | Motor-driven DC circuit breaker | Motor-driven DC circuit breaker | Motor-driven DC switch-disconnector |
| Output side disconnection device | AC circuit breaker | AC circuit breaker | AC circuit breaker |
| DC overvoltage protection / AC overvoltage protection | Surge arrester type II / surge arrester type I | Surge arrester type II / surge arrester type I | Surge arrester type II / surge arrester type I |
| Grid monitoring | yes | yes | yes |
| Ground fault monitoring / Remote ground fault monitoring | opt. / — | opt. / — | opt. / — |
| Insulation monitoring | opt. | opt. | opt. |
| Galvanic isolation | yes | yes | yes |
| Surge arrester for auxiliary supply | yes | yes | yes |
| General Data | |||
| Dimensions (W / H / D) |
2120 / 2400 3) / 850 mm (83.5 / 94.5 / 33.5 inch) |
2120 / 2400 3) / 850 mm (83.5 / 94.5 / 33.5 inch) |
2120 / 2800 3) / 850 mm (83.5 / 110.3 / 33.5 inch) |
| Weight | 2070 kg / 4563 lb | 1170 kg / 2580 lb | 2800 kg / 6173 lb |
| Operating temperature range | -20 °C ... +40 °C / -4 °F ... +104 °F | -20 °C ... +40 °C / -4 °F ... +104 °F | -20 °C ... +40 °C / -4 °F ... +104 °F |
| Max. self-consumption (in operation) / self-consumption (at night) | 1500 W / < 80 W | 1500 W / < 80 W | 2500 W / < 70 W |
| External auxiliary supply voltage | 230 / 400 V (3 / N / PE) | 230 / 400 V (3 / N / PE) | 230 / 400 V (3 / N / PE) |
| External back-up fuse for auxiliary supply | B 16 A, 3-pole | B 16 A, 3-pole | B 16 A, 3-pole |
| Cooling concept | Forced cooling | Forced cooling | Forced cooling |
| Degree of protection: electronics / connection area (as per IEC 60529) | IP20 / IP20 | IP20 / IP20 | IP20 / IP20 |
| Application | Not air-conditioned indoors | Not air-conditioned indoors | Not air-conditioned indoors |
| Maximum permissible value for relative humidity (non-condensing) | 15 % ... 95 % | 15 % ... 95 % | 15 % ... 95 % |
| Maximum operating altitude above MSL | 1000 m | 1000 m | 1000 m |
| Fresh air consumption | 4200 m³/h | 3500 m³/h | 6500 m³/h |
| Features | |||
| DC terminal / AC terminal | Ring terminal lug / ring terminal lug | Ring terminal lug / ring terminal lug | Ring terminal lug / ring terminal lug |
| Display | LC text display | LC text display | LC text display |
| Communication protocols / Sunny String-Monitor | Ethernet / RS485 | Ethernet / RS485 | Ethernet / RS485 |
| Analog inputs / overvoltage protection for analog inputs | 2 x A_in 4) / opt. | 2 x Ain 4) / opt. | 2 x Ain 4) / opt. |
| Certificates and approvals (more upon request) 5) | EN 61000-6-2, EN 61000-6-4, CE conformity, EEG conformity, R.D. 1663 / 2000 | EN 61000-6-2, EN 61000-6-4, CE conformity, EEG conformity, R.D. 1663 / 2000 | EN 61000-6-2, EN 61000-6-4, CE conformity, EEG conformity, R.D. 1663 / 2000 |
| Type designation | SC 250 | SC 250HE | SC 350 |
|
1) At 1.05 VAC, nom and cos φ= 1 2) Efficiency measured without an internal power supply 3) The switch cabinet is raised by 210 mm for the EVR option 4) Terminal for an analog sensor provided by the customer in two-wire and four-wire version 5) EEG conformity: grid management and static voltage support |
Additional Information
- manufacturer: SMA Solar Technology / Germany /